Sizing a 48 V battery

A badly sized pack shows itself quickly: either it cuts out the first time a pump starts, or it costs twice what it should have. The method below avoids both. It needs paper and a calculator, and it starts from your installation, not from a catalogue.

In this article
  1. Step 1: your daily energy, in kWh
  2. Step 2: how many days of autonomy
  3. Step 3: from usable energy to gross energy
  4. Step 4: the voltage, hence the series count
  5. Step 5: the peak current, hence the BMS
  6. Step 6: the space and the mass

Step 1: your daily energy, in kWh

Everything starts here, and everything else follows. List what the battery must power at night or during an outage, with each appliance’s power and the number of hours.

A common example: five 10 W lamps for 5 h, a 150 W fridge running a third of the time over 24 h, an 80 W television for 4 h, a 60 W fan for 8 h, and a 750 W pump for 1 h. That gives 0.25 + 1.2 + 0.32 + 0.48 + 0.75, a little over 3 kWh.

Count in kilowatt-hours, never in amp-hours at this stage. Amp-hours depend on voltage, and the voltage is not chosen yet. This is the most frequent mistake: we are asked for a 200 Ah pack without being told at what voltage, and the question means nothing until that is settled.

If you do not know your consumption, read your meter, or your inverter’s counter, over a week. A measurement beats an estimate, and the gap is often two to one.

Step 2: how many days of autonomy

One day of autonomy means the pack gets through the night and recharges the next day. Two days mean it survives an overcast day with no useful sun. In Benin the rainy season is the argument for two days; cost is the argument against, and it is a serious one: you double the pack for a few days a year.

A middle position often holds up better: one day of autonomy, plus a generator or the grid for the genuinely black days. Let us take a bigger case than the one above, so the numbers speak: a house at 10 kWh a day.

Step 3: from usable energy to gross energy

An LFP cell is not emptied: you take 80% and leave the rest, which is precisely what buys the thousands of cycles. The energy to install is therefore your need divided by 0.8.

For 10 kWh a day over one day, that means 12.5 kWh gross at minimum. The site’s sizing assistant, which applies exactly that rule, proposes 16S1P in 230 Ah prismatics: 16 cells, 51.2 V nominal, 11.78 kWh gross and 9.42 kWh usable.

You will notice 9.42 is slightly under the 10 kWh asked for. That is the catalogue’s step, the next cell up being a jump. This is exactly the kind of trade-off to settle on a quote: one day of autonomy with tight evenings, or the size above.

Step 4: the voltage, hence the series count

An LFP cell is 3.2 V nominal. A "48 V" LFP is sixteen cells in series, so 51.2 V nominal and a real range of 40 V to 58.4 V depending on state of charge. That is a trade convention, not a calculation: 48 divided by 3.2 would give fifteen cells, which nobody builds.

Check that your inverter accepts that range. Most 48 V inverters accept 40 to 60 V, but not all, and an inverter that cuts out at 44 V denies you the bottom third of your pack — you will have paid for capacity you never use.

  • 12 V LFP: 4 cells in series, 12.8 V nominal.
  • 24 V LFP: 8 cells, 25.6 V.
  • 48 V LFP: 16 cells, 51.2 V.
  • 60 V LFP: 20 cells, 64 V. 72 V LFP: 24 cells, 76.8 V.

In NMC the counts differ: 3.6 V per cell, so thirteen cells for a 48 V. For a fixed solar pack, LFP is almost always the right choice, for its cycle life and its heat tolerance. The space NMC saves is of no use when the pack never moves.

Step 5: the peak current, hence the BMS

This is the step people skip, and the one that makes packs cut out. A BMS is sized on peak current, not on average power.

A 5 kW inverter at 48 V draws 5,000 divided by 51.2, that is 98 A in steady state. When a motor starts — pump, fridge compressor, air conditioner — the inrush reaches two to three times nominal for a few hundred milliseconds. A BMS rated at 100 A trips, the television goes dark, and the owner concludes the battery is bad.

For the 16S1P pack above, the assistant proposes 150 A. For the two-day version — 16S2P, 32 cells, 23.55 kWh gross and 18.84 kWh usable — it proposes 250 A: twice the cells in parallel, so twice the current available, and a BMS that keeps up.

Check the cable size between pack and inverter too. At 98 A an undersized cable heats up and drops voltage at exactly the moment it matters, which is during the peak.

Step 6: the space and the mass

The 16S1P pack weighs 75.4 kg, the 16S2P weighs 150.9. That is not a detail: a 150 kg pack does not go on a shelf, and it does not get moved by two people.

Measure the location before ordering, height included, and plan access to the terminals for the day a connection needs retightening. A prismatic pack mounts upright or flat, never on the terminal side.

The figures in this article — configuration, usable energy, BMS rating, mass — come from the same calculation function as the site’s sizing assistant. Enter the same data and you will get the same results, to the digit. That is deliberate: two calculations that diverge make a quote you can no longer defend.

Also worth reading

  • Lead or LFP: the real ten-year cost

    Why a lead-acid bank costs more than an LFP pack over ten years, worked out in cycles and delivered energy rather than in currency.

  • The BMS explained simply

    What a BMS actually does, what it does not do, and the arithmetic showing what a single weak cell costs an entire pack.

All notes

Quote

Your request

The fields marked optional really are. Fill in what you know.

No prices online: every requirement differs, so every quote is priced on its own.

My quote request