The question comes up on every quote: "lithium costs more, is it worth it?" The answer is not decided by the purchase price, it is decided by how many times you will buy again. Here is the arithmetic, set out with the typical values of both technologies.

In this article
  1. Why we do not answer in currency
  2. What a cycle means on each side
  3. The ten-year arithmetic
  4. What lead costs on top, where nobody looks
  5. Where lead still makes sense
  6. What to check before switching

Why we do not answer in currency

This site posts no prices, and that is not a pose: a cell price depends on the batch, the quantity and the moment, and a posted price would be wrong for almost everyone. The ratio between two technologies, however, depends on neither batch nor moment. So ratios are what we reason with here, and you apply your own prices.

This way of counting has one advantage: it survives inflation and commodity swings. The day lithium drops twenty per cent, the reasoning below does not change by a line.

What a cycle means on each side

A cycle is one charge and one discharge. But the two technologies do not count the same thing under that word, and that is where most of the gap comes from.

A sealed lead-acid battery does not tolerate being emptied. Manufacturers typically quote around 500 cycles at 50% depth of discharge; past that, life collapses. On a bank rated 200 Ah at 12 V you therefore have only half of it, which is 1.2 kWh usable per cycle.

An LFP cell accepts being taken to 80% every day. With four 230 Ah prismatic cells in series — a standard 12 V — you have 2.36 kWh usable per cycle, and the manufacturer typically quotes 5,000 cycles under those conditions.

Both numbers are typical manufacturer values, not measurements we made. The values for the batch we deliver are on the quote, and a test report comes with every pack we assemble.

The ten-year arithmetic

Multiply usable energy by cycle count. That is the total energy the battery will have delivered before it is due for replacement.

  • Lead 200 Ah at 12 V: 1.2 kWh × 500 cycles = 600 kWh over its whole life.
  • LFP 4S 230 Ah: 2.36 kWh × 5,000 cycles = 11,776 kWh over its whole life.

The ratio is close to twenty to one. Put another way, for the same delivered energy you will need some twenty lead banks where one LFP pack is enough.

Look at it in time instead. A home solar kit typically runs one cycle a day. Ten years is 3,650 cycles. The lead bank lasts 500 cycles, so eight successive banks are needed. The LFP pack lasts 5,000, so one is enough, with margin.

Even if the LFP pack costs you three or four times a lead bank — the usual order of magnitude — you are ahead by the third or fourth replacement, which is to say before year five. And that reckoning still ignores everything below.

What lead costs on top, where nobody looks

Three items appear on no invoice and still weigh heavily.

  • Round-trip efficiency. A lead bank typically returns 80 to 85% of what you put in; an LFP cell, 95% and more. On a solar kit that gap is paid for in extra panels, bought once and for nothing.
  • Mass. The lead bank in our example weighs about sixty kilograms; the four equivalent LFP cells, 16.4 kg. Multiply by eight replacements and count the freight, the handling, the frame to build.
  • Charging. Lead needs a long absorption phase, often hours at constant voltage, during which it accepts only a small current. In the rainy season, with four useful hours of sun, that phase never finishes — and a lead battery never filled sulfates, so it dies before its 500 cycles.

That last point is the one we see most in the field. A lead bank installed in Benin rarely reaches its 500 cycles, because it is rarely fully recharged. The arithmetic above is therefore generous to lead.

Where lead still makes sense

There are such cases, and hiding them would be lying to you.

  • Pure standby, a few discharges a year. At ten cycles a year a lead bank lasts for years and its purchase advantage is never caught up.
  • An older inverter whose charger offers no lithium profile and that you do not want to replace. Charging LFP on a lead curve is possible but poorly matched, and a lead float voltage held permanently on LFP wears it for nothing.
  • A budget that leaves no choice today. A lead bank that works beats a lithium pack you do not buy.

What to check before switching

If you move to lithium, three points are checked before ordering, not after.

  • Does your inverter accept a lithium profile, or at least adjustable charge voltages? A 48 V LFP charges at 56.0-57.6 V and must not be held at a high float.
  • Will the pack have a BMS sized for the inverter’s peak current, not for its nominal power? A 3 kW inverter at 48 V draws 62 A continuously, and twice that when a motor starts.
  • Where will the pack sit? Heat is the first ageing factor, and a plant room under a metal roof in Cotonou is not a garage in Europe.

Describe your installation to us rather than the battery you think you want: the voltage, the daily energy, the peak current and the space available. The pack follows from that, and we will tell you whether your inverter can keep up.

Also worth reading

  • Sizing a 48 V battery

    The six-step method, with one example worked end to end: from daily consumption to the cell count and the BMS rating.

  • Lithium batteries above 35 °C

    Why a datasheet quoted at 25 °C does not describe your installation, and the six decisions that change in the Beninese climate.

All notes

Quote

Your request

The fields marked optional really are. Fill in what you know.

No prices online: every requirement differs, so every quote is priced on its own.

My quote request