Maintaining and storing a lithium battery

A lithium battery needs no maintenance in the sense lead did: there is no water to top up, no terminals to scrape every month. But it needs two things, and ignoring them costs a whole pack. Here is what they are, and what happens during a long outage.

In this article
  1. The two enemies: a full charge and a deep discharge
  2. The self-discharge arithmetic
  3. What happens during a long outage
  4. The routine, fifteen minutes a quarter
  5. The disconnect, the accessory everyone forgets
  6. Bringing a stored pack back

The two enemies: a full charge and a deep discharge

A stored lithium cell ages, and it ages faster the fuller it is. At 100% charge the voltage across the electrodes is at its maximum, and the parasitic reactions that consume available lithium run faster. In the heat, faster still.

At the other end, a cell left to empty completely drops below the voltage at which the collector’s copper starts to dissolve. The damage is irreversible, and it is invisible: the cell seems to recharge normally, then develops an internal short weeks later.

The ideal storage point is therefore in the middle: around 50% charge, cool, and with nothing connected to it.

This is the exact opposite of lead, which had to be stored full and recharged regularly or it sulfated. A habit learned on lead damages a lithium pack, and it is the mistake we see most often.

The self-discharge arithmetic

A lithium cell typically loses 2 to 3% of its charge per month, powering nothing. Take the high value, 3%, and see where it leads.

  • A pack stored at 50% falls to 42% after six months, and 35% after a year. It stays in the right window, and it wakes up without trouble.
  • A pack stored at 20% — because it was taken out after an outage and never recharged — falls to 17% after six months. That is below the low threshold of many BMS: the pack no longer wakes, and some chargers then refuse to start.
  • A pack stored full is still at 83% of its charge after six months. It is in no immediate danger, but it will have spent six months at the voltage that wears it most.

These figures assume a disconnected pack. With a BMS connected, add its own standby draw — a few milliamps, which is a few per cent more per month on a small pack, negligible on a large one.

A zem pack pulled at the end of a season and forgotten in a workshop is the classic total loss. Six months, a BMS on standby, a low starting charge, and it does not come back.

What happens during a long outage

In Benin the question is not theoretical. Three situations recur, and they do not call for the same thing.

  • The short outage, a few hours. The pack works; that is its job. Nothing to do, except check that the inverter cuts out before the BMS low threshold rather than relying on the BMS to arbitrate.
  • The long outage with sun. The pack cycles deeply every day. It is the hardest use, and it is what LFP is for. Watch the spread between cells at end of charge.
  • The long outage without sun, or a prolonged absence. This is where you intervene: if the pack is getting low and no recharge is in sight, isolate it at the disconnect rather than letting it drain to the BMS threshold.

The habit to build is this one: a pack you can no longer recharge gets disconnected, not left to finish itself.

The routine, fifteen minutes a quarter

Four actions, and they need only a multimeter and a wrench.

  • Read each cell’s voltage at end of charge, pack full. They should sit within a few tens of millivolts. Write the values down somewhere: it is the drift that speaks, not the isolated reading.
  • Retighten the bolted connections, to the torque the cell manufacturer specifies. A connection that loosens heats up, and a connection that heats up loosens further. It is the single most useful maintenance action.
  • Dust, dry, without blowing dust towards the connections. A layer of dust is thermal insulation laid over the thing you want to cool.
  • Look. A swelling cell, a browning wrapper, a green trace on a terminal: all three are visible to the eye and none of them lies.

Once a year, add a capacity test: full charge, discharge at a known power, stopwatch. Compare with the test report delivered with the pack. It is the only way to know where you actually stand.

The disconnect, the accessory everyone forgets

Everything above assumes you can isolate the pack. Many installations we see have no way of doing so other than unscrewing a lug under load, which is exactly what must not be done.

A disconnect switch rated for the pack current, fitted on the main output, changes three things: you can isolate the pack before an absence, work on the installation without working live, and cut quickly if something goes wrong.

The BMS does not fill that role. A BMS cuts on fault, through its transistors, and it stays conducting if one of them fails short. The disconnect is a mechanical break, visible, and it is the only one you can put a hand on with confidence.

Bringing a stored pack back

Do not reconnect it to the installation all at once. Measure each cell’s voltage first: if one is clearly below the others, it is recharged separately, at low current, before the pack goes back together.

Then recharge at reduced current for the first cycle, and run one full cycle to let the BMS re-reference its state-of-charge estimate. A pack returning to service often displays nonsense for a charge or two.

A pack that has dropped below its BMS low threshold does not "wake up" by forcing it. If yours is in that state, tell us what you measure at the terminals and cell by cell: some cases recover cleanly, others do not, and the point is not to attempt a recharge that would make things worse.

Also worth reading

  • Lithium batteries above 35 °C

    Why a datasheet quoted at 25 °C does not describe your installation, and the six decisions that change in the Beninese climate.

  • The BMS explained simply

    What a BMS actually does, what it does not do, and the arithmetic showing what a single weak cell costs an entire pack.

All notes

Quote

Your request

The fields marked optional really are. Fill in what you know.

No prices online: every requirement differs, so every quote is priced on its own.

My quote request